FAHRENHEIT 10000 LAB
Fahrenheit 10000 Laboratory performs temperature-rise, electrical and mechanical operation tests on low-voltage equipments with alternative or direct current.
Fahrenheit 10000 Laboratory is accredited by COFRAC in compliance with NF EN ISO/IEC 17025 standards. It guarantees its skills and impartiality by its quality system management.
Tests performed in Laboratory are based on normative methods, with following characteristics:
- Current: up to 6300 A
- Number of measuring points: up to 170
- Size of tested object: 4900 mm x 3000 mm x 2750 mm
The laboratory can run the following tests under accreditation
Test | Method reference | Laboratory characteristics | Resolution |
Temperature-rise test |
IEC 61439-1 NF EN 61439-1 NF EN IEC 61439-1 NF EN 50123-1 |
Current: Up to 6300 A AC at 10V 630 A AC at 40 V 250 A AC at 80 V 6000 A DC at 10 V Number of measuring points: up to 170 Frequency: 50/60 Hz Ambient temperature: from 20 to 35 °C |
0,01 °C |
Power-frequency withstand voltage test |
IEC 61439-1 NF EN 61439-1 NF EN IEC 61439-1 NF EN 50123-1 |
0 to 5 kV (61439-1) 0 to 15 kV (50123-1) |
1 µA |
Insulation test |
IEC 61439-1 NF EN 61439-1 NF EN IEC 61439-1 |
Up to 1 MΩ | 0.1 V |
Clearances and creepage distances test |
IEC 61439-1 NF EN 61439-1 NF EN IEC 61439-1 |
Imperial and Metric Up to 150 mm |
0,01 mm |
Effective earth continuity between grounds test |
IEC 61439-1 NF EN 61439-1 NF EN IEC 61439-1 |
0.1 Ω under 10 A | 100 nΩ |
Mechanical operation test |
IEC 61439-1 NF EN 61439-1 NF EN IEC 61439-1 IEC 61439-2 NF EN 61439-2 NF EN IEC 61439-2 NF EN 50123-1 |
Manual Automated |
N / A |